КУБАНЬКАБЕЛЬ

Banner Image

Products

Installation wires and cables КУИН-Пу (wire)
manufactured acc. to ТУ 3551-023-76960731-2012

КУИН-Пу wires conform fully to the new GOST R 53768-2010 "Wires and cables for electrical equipment of rated voltage up to and including 450/750 V. General specifications" which has replaced the GOST 6323-79 on 01.01.2011 wherefore wires ПВ1, ПВ2, ПВ3, ПВ4, ППВ, АПВ and АППВ under GOST 6323-79 can no longer be used on the territory of the Russian Federation.

Area of application

  • lighting mains;
  • electric equipment installation, machines mounting, machinery and machine tools of rated voltage up to and including 450/750 V AC with frequency up to 400 Hz or steady voltage up to 1000 V DC mounting.

Cables and wires are designed for fixed cabling indor and outdor premises, for wires installation under plaster, into concrete, brick laying, building constructions air void as well as for surface on-walls and on-ceiling wiring and wiring in other constructions, some of which require extra-flexibility.

Cables and wires can be used in all classes and all explosive hazardous areas (under GOST R IEC 60079-14-2008).

Fire-resistant cables and wires can be used in all electric plants requiring fire resistance under FL №123 "Technical regulations on fire safety requirements" and GOST R 53315-2009 "Cable products. Requirements of fire safety". Primary wires and cables application fields with a glance to their modification and fire safety class are listed in table 5.

Performance specifications

  • Extra-flexible wires and cables conductors - copper stranded 5 class conductors under GOST 22483, flexible conductors - 1 or 2 class
  • Wide temperature application range:
    • from -60° to +70°C for cables marked with "ХЛ"
    • from -60° to +125°C for cables marked with "Т"
    • from -50° to +200°C for cables marked with "Т-Т"
    • from -50° to +70°C for other types
  • The lowest temperature limit for installation, not lower than:
    • -30°С for cables marked with "ХЛ" or "Т"
    • -15°С for other types of wires and cables
  • Modification B, placement category 1-5 (under GOST 15150). Wires use is possible in all macroclimatic areas including tropics.
  • "УФ" - resistant to solar irradiation
  • "в" - protection against damp expansion under cover
  • "М" - oil-and-petrol resistant jacket
  • Wires and cables may have:
    • shield made of copper wires or AlumoFlex
    • armour made of zinc-coated steel wires
  • Conductors resistance to direct current conforms GOST 22483
  • Rated voltage
    • for wires: ~From 450/750 V to 400 Hz or -1000 V
    • for cables: ~300/500 V frequency up to 400 Hz
  • Electrical insulation resistance at a temperature of +20°C not less than 5 МОhm•km
  • Voltage test under GOST 23286-78:
    • insulated conductors for transmission under category ЭИ-2
    • wires ~2500 V 50 Hz within 5 min under ЭИ-1
    • cables ~2000 V 50 Hz within 5 min under ЭИ-1
  • Fire-resistant wires and cables remain functional under fire conditions at least 90 minutes (ПО4 under GOST R 53315-2009)
  • Wires and cables with combustion products of low toxicity "LTx" - are the best fire safety factor

Cable design

Multi-conductor wires have flat form. Electric conductors are made of copper tin-coated "л" and untinned wire. Extra-flexible wires and cables "Г" have a 5 class conductor under GOST 22483. Electrical conductors’ classes are specified in table 1.

Fire resistant wires "FR" have got mica tape wound under an conductor insulation - this is the safest fire protection method at the moment.

Wires may have shield made from copper wire - "Эм" index, tinned copper wire - "Эл" index, or aluminium foil film with copper tinned conductor - "Э" index.

The jacket of multi-conductor wire fills gaps between conductors giving flat shape to it.. Wires may have a water swelling element "в" preventing unguided propagation of moisture under a wire jacket. Solid wires may be made without a jacket (in such a case jacket material is not necessary to be specified). Wires may have armour made of zinc-coated steel wires "К". Over armour there is a cable jacket overlaid. Conductors' insulation and jacket can be made of PVC compound "В", halogen free polymer compound "П" or thermoelastoplastic "Т". Insulation and jacket materials are listed in table 4 as well as corresponding fire safety indexes. Cables can be produced with combined conductor cross-section under customised order.

Cable marking when ordering:

КУИН-Пу x - -
1 2 3 4 5 6 7 8 9 10 11 12
  1. Flexibility:
    • "-" - common flexibility
    • "Г" - extra flexibility
  2. Insulation material :
    • "В" - PVC compound
    • "П" - polymer compounds
    • "Т" - thermoelastoplastic
    • Fire safety performance depending on material - see table 4
  3. Collective shield:
    • "-" - without collective shield
    • "Э" - AlumoFlex
    • "Эм" - copper untinned wires
    • "Эл" - copper tinned wires
  4. Armor under an external jacket:
    • "-" - without armour
    • "К" - shield from zinc-coated steel wires
  5. Jacket material:
    • "В" - PVC compound
    • "П" - polymer compounds
    • "Т" - thermoelastoplastic
    • Fire safety performance depending on material - see table 4
  6. Type of fire protection modification:
    • "-"
    • "нг(A)"
    • "нг(A)-LS"
    • "нг(A)-HF"
    • "нг(A)-LSLTx"
    • "нг(A)-HFLTx"
    • "нг(A)-FR"
    • "нг(A)-FRLS"
    • "нг(A)-FRHF"
    • "нг(A)-FRLSLTx"
    • "нг(A)-FRHFLTx"
    • Type depends on jacket and insulation materials - see table 4
  7. Conductors number:
    • "1..3" - in a wire
    • See all combinations in table 2
  8. Conductor area, mm²:
    • "0.5..400" - for wire
    • Full range of sizes is described in table 2.
  9. Copper conductor tin coating:
    • "-" - untinned conductor
    • "л" - tinned conductor
  10. Earthing conductor and neutral conductor presence *:
    • "-" - without earthing conductor and neutral conductor
    • "(PE)" - earthing conductor
    • "(N)" - neutral conductor (only in cable)
    • "(PE,N)" - earthing conductor and neutral conductor (only in cable)
  11. Water-blocking element under a shield:
    • "-" -without water-blocking element
    • "в" - with water-blocking element
  12. Special indexes if there are several indexed they should be specified:
    • "-" - without special index
    • "ХЛ" - cold-resistant version, exploitation at a temperature from -60°С (only for "нг(A)" version and "В" material)
    • "УФ" - solar radiation resistant (only for "нг(A)-HF" version or "Т" material)
    • "Т" - thermoelastoplastic with increased heat resistance, up to +200°С (only for "Т" material)
    • "М" - oil-and-petrol resistant jacket(only for "нг(A)-HF" version or "Т" - material)

* they add number and earthing conductor nominal cross-sectional area for cables with smaller earthing conductor nominal cross-sectional area For instance: КУИН-КуГВВнг(A) 3х25 + 1х16(PE).
In 3-, 4- and 5-conductors cables a 16mm² earthing conductor is assumed with common conductors' area 25mm² and 35mm², and 25mm² earthing conductor is assumed with common conductors' area 50mm².

An example of cable marking when ordering

Wire КУИН-ПуВ 1х2,5 ТУ 3551-023-76960731-2012
- Installation wire with one 2.5mm² electric conductor, non-rigid PVC insulation, without shield..

Table 1. Copper electrical conductor class.

Electrical conductor nominal cross-sectional area, mm²

Copper conductor class under GOST 22483-77

for wires

common conductors

flexible conductors

0,5

1 or 2

5

0,75 - 10

16 - 50

2

70 - 400


Table 2. Quantity and nominal cross-sectional area of conductors.

Conductors quantity

Conductors nominal cross-sectional area, mm²

for wires

1

0,5; 0,75; 1,0; 1,5; 2,5; 4; 6; 10; 16; 25; 35; 50; 70; 95; 120; 150; 185; 240; 300; 400

2, 3

0,5; 0,75; 1,0; 1,5; 2,5; 4

4, 5

-


Table 3. Colouring of insulated conductors.

Conductors quantity

Colouring of insulated conductors

3

brown, black, grey

brown, blue, yellow green

4

brown, black, grey, blue

brown, black, grey, yellow green

5

brown, black, grey, blue, black

brown, black, grey, blue, yellow green


Table 4. Fire safety index according to material of jacket and insulation.

Jacket and insulation material

Fire safety index

Jacket and insulation material (if any) of installation wires and cables

В

(no index)

insulation and jacket - PVC compound

нг(A)

insulation - PVC compound -, jacket - low flammability PVC compound

нг(A)-LS

insulation and jacket from low fire hazard PVC compound

нг(A)-LSLTx

insulation and jacket - low fire hazard PVC compound with low toxicity of combustion products.

нг(A)-FRLS

fire-resistant; insulation and jacket - low fire hazard PVC compound

нг(A)-FRLSLTx

fire-resistant; v and jacket - low fire hazard PVC compound with low toxicity of combustion products.

П

нг(A)-HF

insulation and jacket - halogen-free polymer compounds

нг(A)-HFLTx

insulation and jacket - halogen-free polymer compounds with low toxicity of combustion products.

нг(A)-FRHF

fire-resistant; insulation and jacket - halogen-free polymer compounds

нг(A)-FRHFLTx

fire-resistant; insulation and jacket - halogen-free polymer compounds with low toxicity of combustion products.

Т

нг(A)

insulation and jacket - thermoelastoplastic

нг(A)-FR

fire-resistant; insulation and jacket - thermoelastoplastic


Table 5. Primary designated areas of installation for wires and cables with account of their modifications and fire safety class under GOST R 53315-2009 and GOST R 53768-2010.

Modification

Fire safety class

Primary designated area

no marks

О1.8.2.3.4

For single cable lines routing and running of feed circuits of bow collectors located in premises.

нг(A)

П1б.8.2.5.4

For routing, with account of combustible content loading, in open cable structures (racks, galleries) of external electric installations.

нг(A)-LS

П1б.8.2.2.2

For cable lines bunched wiring in indoor electrical installation premises. For electric installations of residential and public buildings.

нг(A)-HF

П1б.8.1.2.1

For cable lines and electric installations in case of bunched or single wiring in office premises fitted out with computer equipment and microprocessor engineering as well as in buildings and facilities with mass stay of people including multifunctional high-rise buildings, complexes and sports facilities.

нг(A)-LSLTx

П1б.8.2.1.2

For electric installations in public buildings and children preschool institutions and educational institutions, specialized homes for the elderly and disabled, hospitals, boarding educational institutions bedroom blocks and children institutions.

нг(A)-HFLTx

П1б.8.1.1.1

нг(A)-FRLS

П1б.7.2.2.2

For wiring in fire protection systems and other systems that must remain functional under fire conditions.

нг(A)-FRHF

П1б.7.1.2.1

нг(A)-FRLSLTx

П1б.7.2.1.2

For wiring in fire protection systems and other systems that must remain functional under fire conditions, in children preschool institutions and educational institutions buildings, specialized homes for the elderly and disabled, hospitals, boarding educational institutions, bedroom blocks and children institutions.

нг(A)-FRHFLTx

П1б.7.1.1.1